127


127





 
Dimensions
 
Internal connection diagrams
   
Single pole thermal circuit breaker with push-to-reset, tease-free, trip-free, snap action mechanism (R-type TO CBE to EN 60934; M-type when fitted with optional manual release feature). Available in versions for plug-in or integral mounting, track mounting, or with a frame for snap-in panel mounting. The optional KF housing is particularly suited to high humidity and other damp conditions.
Approved to CBE standard EN 60934 (IEC 60934).
 
Voltage rating: 
  • AC 250 V
  • DC 28 V
  • UL: DC 50 V
Current ratings: 
from 0.05 A to 25 A  
Number of poles: 
single pole 
Mounting method: 
flange 
socket 
rail mounting 
Terminal design: 
blade terminals 
screw terminals 
Actuation: 
manual release 
push button 
Auxiliary contacts: 
without auxiliary contacts 
Water splash protection: 
without water splash protection 
Illumination: 
without illumination 
Typical life:
0.05...16 A 5,000 operations at 2 x IN, inductive
17...25 A 5,000 operations at 2 x IN, resistive
Interrupting capacity Icn:
type F:
0.05...2.5 A. 8 x IN
3...5 A: 20 x IN
6...12 A: 200 A
13...25 A: 400 A
type T:
0.05...2.5 A: 8 x IN
3...5 A: 20 x IN
6...25 A: 400 A
Approvals:
VDE, CSA, UL, CCC
(Type 127-T.. approvals N/A)

Datasheet Downloads

download  Series 127 Thermal Circuit Breaker ETA.pdf (318,10 KB)